The KOBOLD POD is a universal plug-on display and signal converter with IO-Link that mounts directly on the M12x1 connector of a process sensor. It reads a pulse, frequency, current, or voltage signal from the sensor, shows the scaled value on a 1.4” color TFT display, and provides two independently configurable outputs including IO-Link. The POD is designed for upgrading or retrofitting existing sensors and needs no separate auxiliary power supply.
What the POD plug-on display adds to a sensor
The POD adds a local readout and two outputs to any sensor with a standardized M12x1 connector that has a matching pin layout, with the signal on pin 4. It sits between the sensor and the control system, interprets the sensor signal, scales it, and presents the result on the display and the configurable outputs. In practice this means an installed sensor can gain local indication and integration into IO-Link networks without being replaced.
The POD is powered from the same 19-30 VDC supply that feeds the sensor, drawing a maximum of 70 mA for itself. The sensor power consumption when connected to the POD should be a maximum of 20 W if IO-Link is not being utilized and 3 W if IO-Link is used.
Sensor inputs: pulse, frequency, current, or voltage
The POD accepts pulse and frequency signals from 0.1 to 2500 Hz (NPN, PNP, NAMUR, Reed, Hall, and active outputs), current signals from 0 to 25 mA, and voltage signals from 0 to 25 V. Both 2-wire and 3-wire sensors can be connected to the device.
The input is fully programmable, so standard ranges such as 4-20 mA, 0-5 VDC, 1-5 VDC, and 0(2)-10 VDC are configured during setup. Scaling for linear signals can be achieved by correlating an input signal value to a process value, typically the full scale value. The sensor characteristic curve can be reproduced in the POD with up to 10 points for greater accuracy for non-linear input signals.
Because compatibility rests on the signal and the connector rather than the brand, the POD can also be configured for sensors from other manufacturers, provided that the electrical specifications and signals are compatible.
Two configurable outputs with IO-Link
Each of the two outputs is set independently as an active analog output (4-20 mA, 0-20 mA, 2-10 V, or 0-10 V), a switching output (NPN, PNP, or Push-Pull, up to 30 VDC and 200 mA, short-circuit proof), a scalable pulse output (frequency/pulse generating flow meters only), or a scalable frequency output.
Output 1 can also be utilized for IO-Link communication enabling digital multi-value data transmission of the primary variable (flow, temperature, pressure, etc.), volume for flowmeters that generate pulse/frequency signals, and two status bits. With IO-Link mode selected, the POD offers bi-directional data exchange with an IO-Link master allowing parameters and other functions to be set over the connection.
Totalizing and dosing for pulse-output flow meters
When the connected sensor is a flow meter that generates a pulse or frequency output, the POD measures volume as well as the rate, keeping both a partial and a total quantity counter. There is also an optional batching mode with Output 1 functioning as an external control input: a 0.5 to 4 second high signal on the control input starts or stops dosing, a signal longer than 5 seconds resets it, and Output 2 acts as the output driving the dosing valve or pump while the batch runs.
Display, keys, and mounting
The 1.4” color TFT display has 128 × 128 pixels and an adjustable update rate of 0.5 to 10 seconds. Four optical keys handle scaling and setup without mechanical buttons, and the keys can be operated with gloves in most conditions. Hotkeys can be assigned as shortcuts to functions you use often.
The display orientation can be digitally rotated in 90° steps, and the housing itself rotates 300° around the connector axis, so the readout can be aligned to the installation whichever way the sensor points. The orange PA housing with nickel-plated brass connector is rated IP67 and tested for shock and vibration to DIN EN 60068-2-27 and DIN EN 60068-2-6.
Typical applications
The POD is designed for installations where an existing sensor needs a local display, a second output, or an IO-Link connection without replacing the sensor. Typical uses include providing a local display for products with only blind outputs, adding totalizing for frequency/pulse-output flow meters, or converting an older analog 4-20 mA or 0-10 V transmitter signal into IO-Link for system upgrades without purchasing new instrumentation.
Optional accessories
Optional accessories are available separately. The ZUB-POD-WMK stainless steel wall mount kit lets the POD be mounted on a wall or panel away from the sensor. The ERS-ZOK-529001, 2” pipe mounting kit, combined with the ZUB-POD-WMK, allows the POD to be mounted remotely to a pipe instead. The ZUB-KAB-22K005 sensor cable (M12 plug to M12 coupling, 4-pin, 16.4 ft / 5 m PVC) makes the connection to the remote sensor for these configurations.
Common Questions for POD - Universal Plug-on Display and Signal Converter with IO-Link
The POD plugs onto the sensor’s M12x1 connector in place of the normal cable, and the system cable then plugs into the POD’s own M12x1 output connector. If the sensor sits somewhere hard to see, connect the POD through an extension cable up to 65.6 ft (20 m) long and mount it on a wall or pipe with the optional kits.
No. The POD runs on the 19-30 VDC supply already present on the system cable and draws at most 70 mA for itself. The sensor still receives its voltage and ground through the POD’s sensor-side connector, so a sensor that was powered from that cable before continues to be powered the same way.
Three signal families: pulse or frequency at 0.1 to 2500 Hz (NPN, PNP, NAMUR, Reed, Hall, or active), current at 0-25 mA, and voltage at 0-25 V. The input is programmable, so common standard ranges such as 4-20 mA, 0-10 V, or 1-5 V are selected during setup rather than ordered as a fixed version.
What matters to the POD is the signal and the connector, not the brand on the sensor. A third-party device with a current, voltage, pulse, or frequency on an M12x1 connector with the signal on pin 4 and compatible electrical specifications can be used with the POD.
Analog (4-20 mA, 0-20 mA, 2-10 V, or 0-10 V), switching (NPN, PNP, or Push-Pull at max. 30 VDC and 200 mA), pulse (frequency/pulse sensors only), or frequency can be chosen separately for each of the two outputs. Output 1 also offers IO-Link communication mode. For flow sensors with frequency/pulse signals, a dosing function is available where Output 1 functions as a control input and Output 2 is used as the dosing output.
Yes. IO-Link is one of the communication modes available on Output 1. Select it during setup and the POD then enables communication with an IO-Link master over that output. This allows for multi-value digital data transmission, bidirectional communication, and remote device configuration.
Yes, with a pulse- or frequency-output flow meter. The POD keeps separate partial and total counters, and its pulse output can be scaled to either. For batching, a control input on Output 1 starts, stops, or resets the dose, and Output 2 goes high for the duration of the batch.
Linearity is 0.15 % of the measured value, and temperature drift stays within that figure. The high/low switching threshold for pulse inputs is approximately 1.1 V. Up to 10 curve points can be entered for non-linear process signals so that the POD display values follow the sensor’s actual characteristic curve more closely.
The housing is rated IP67 and tested to 20 g shock (11 ms) and 5 g vibration (10 to 2000 Hz). The unit measures 4.41 × 3.23 × 2.01 in (112 × 82 × 51 mm) including connectors and weighs 4.9 oz (140 g).
Three items are sold separately: the ZUB-POD-WMK stainless steel wall mount kit, which includes two mounting brackets and fastening screws; the ERS-ZOK-529001, 2” pipe mounting kit, which can be combined with the ZUB-POD-WMK for pipe mounting; and the ZUB-KAB-22K005 sensor cable, a 4-pin M12 plug-to-coupling PVC cable 16.4 ft (5 m) long for connecting the POD to a sensor at a distance.