What Is the DFT Compact Paddle Wheel Flow Sensor?
The KOBOLD DFT is a compact paddle wheel flow sensor for water and low-viscosity liquids. An inlet nozzle directs flow onto the paddle, so it needs no straight pipe runs. It is a smaller, more economical version of the DF series, with a nickel-plated brass or PTFE body and five ranges from 0.05–0.50 GPM to 0.8–15 GPM. The DFT is made in the USA.
The paddle carries a sealed ring magnet that transfers its rotation, without contact, to a Hall sensor mounted on the housing. The Hall sensor outputs a frequency signal proportional to flow rate. An open collector pulse output is standard. Optional KOBOLD electronics can display that signal, convert it to a 4-20 mA or 0-10 VDC analog output, totalize it, or switch up to two limit contacts.
DFT Flow Ranges, Connections, and Accuracy
The DFT comes in five measuring ranges, 0.05–0.50, 0.13–1.8, 0.26–4.0, 0.5–9.5, and 0.8–15.0 GPM, each set by a fixed inlet orifice of 2.0, 4.3, 5.9, 9.0, or 13.5 mm. Accuracy is ±2.5% of full scale, or ±5% on the standard OEM pulse output version (DFT-..0000). Female process connections are 1/4", 1/2", or 3/4" NPT, or G1/4, G1/2, or G3/4, offered by range.
Pressure loss at maximum flow is 8.7 to 11.6 PSI for brass housings and 7.25 to 13.0 PSI for PTFE housings, by measuring range.
Brass or PTFE Body: Which DFT Fits the Liquid?
The nickel-plated brass DFT is designed for water, light chemicals, and low-viscosity liquids below 10 cSt, and is rated to 230 PSIG. The PTFE version is designed to stand up to aggressive chemicals and is rated to 70 PSIG. Both versions operate from -4°F to 176°F (-20°C to 80°C).
Construction materials:
- Housing and cover: brass or PTFE
- Vane: PTFE
- Axle: ceramic (Al2O3) or sapphire
- Bearing: PTFE
- Gasket: NBR (DFT-31/36 models) or FEP-O with silicone (DFT-33/38 models)
- Front and back panels: black-anodized aluminum (DFT-33/38 only; non-wetted)
- Screws: stainless steel
DFT Output and Electronics Options
Every DFT ships with a pulse output, and the same sensor body accepts optional electronics for analog transmission, switching, rate display, totalizing, or batching. All versions carry IP65 electrical protection. The options, with their supply and connection details, are:
- Standard OEM pulse output (..0000): NPN open collector, 5-24 VDC supply, 15 mA maximum sink current, DIN 43650 plug.
- Pulse output F400: PNP open collector, 24 VDC ±20% supply, 20 mA maximum, DIN 43650 plug.
- Analog output L443 or L442: 4-20 mA, 3-wire or 2-wire, 24 VDC ±20% supply, 500 Ω maximum load, DIN 43650 plug.
- MA electronics: 4-20 mA or 0-10 VDC output, 500 Ω maximum load, 24 VDC or 110 VAC supply, 1.5 m (4.9 ft) cable or connector.
- WM electronics: one SPDT switching contact rated 250 V / 5 A maximum, 24 VDC or 110 VAC supply, 1.5 m (4.9 ft) cable or connector.
- K electronics: 8-digit backlit LCD rate display, 4-20 mA or 0-10 VDC analog output, minimum and maximum SPDT contacts rated 24 V / 2 A, 2.5% hysteresis, 24 VDC supply, 1.5 m (4.9 ft) cable.
- E totalizer electronics: 2-line, 8-digit backlit LCD showing rate, total, and grand total, 4-20 mA or 0-10 VDC output, two relays rated 30 V / 1.5 A, 24 VDC supply, 10-pin cable or two M12 connectors.
- G batching electronics: as the E version, with batch, start, stop, reset, fine batch, and correction quantity functions.
Installing the DFT: No Straight Runs, Any Orientation
Because the inlet nozzle directs flow onto the paddle, the DFT needs no upstream or downstream straight piping and can be mounted in any orientation. Mount it tension-free and check the union fitting seals after installation. Exceeding the measuring range by more than 20% can damage the bearing, so confirm the actual flow against the label.
Introduce the liquid slowly at start-up, and keep the housing continuously filled during operation. Pressure surges from solenoid valves, ball valves, or similar devices (water hammer) can break the instrument, and large air bubbles can cause measuring errors or bearing damage. Contact versions should not be installed within an inductive field. Before wiring, confirm the supply voltage and de-energize the supply wires; incorrect plug wiring can destroy the electronics.
Common Questions about DFT - Compact Paddle-Wheel Flow Sensor
A ring magnet embedded in the rotating vane is hermetically sealed from the liquid. As the vane turns, the magnet drives a Hall sensor on the case with no mechanical contact, and the Hall sensor generates a pulse frequency that rises in proportion to flow. Downstream electronics display, convert, count, or switch on that pulse train.
Five ranges cover 0.05 to 15 GPM: 0.05–0.50 GPM, 0.13–1.8 GPM, 0.26–4.0 GPM, 0.5–9.5 GPM, and 0.8–15.0 GPM. Each range is set by the inlet orifice diameter, from 2.0 mm to 13.5 mm. Choose the range that brackets the actual flow, since running more than 20% above range can damage the bearing.
Pressure ratings depend on the body: 230 PSIG for nickel-plated brass and 70 PSIG for PTFE. Either body operates from -4°F (-20°C) up to 176°F (80°C). The sensor must not be run above these limits, and pressure surges in the line should be avoided.
The PTFE body is the version intended for aggressive chemicals. The nickel-plated brass body is intended for water, light chemicals, and liquids with viscosity under 10 cSt. Media for either version should be water or another low-viscosity liquid. Wetted parts in both versions include a PTFE vane and bearing with a ceramic or sapphire axle.
An open collector pulse output (NPN standard, PNP optional) is built in. Optional electronics add an analog signal (4-20 mA or 0-10 VDC), an SPDT relay contact, a backlit LCD rate display with two switch points, or a totalizer or batch controller with two relays plus an analog output.
The standard NPN pulse output runs on 5-24 VDC at 15 mA maximum sink current. The F400, L443, and L442 versions use 24 VDC ±20%. MA, WM, and K electronics take 24 VDC (+15%/-10%), and MA and WM are also offered for 110 VAC ±20%. E and G electronics use 24 VDC ±20% with 100 mA maximum sink current.
No. An inlet nozzle redirects the liquid onto the paddle inside the housing, so the upstream and downstream straight-run requirements that apply to many other paddle designs do not apply here. The DFT can also be installed in any mounting orientation, and it should be mounted into the pipe tension-free.
Female threaded connections come in 1/4" NPT, 1/2" NPT, and 3/4" NPT, plus G1/4, G1/2, and G3/4. Connection size is tied to the measuring range: the three smallest ranges use 1/4" and 1/2" sizes, the 0.5–9.5 GPM range uses 1/2" and 3/4", and the 0.8–15 GPM range uses 3/4".
All DFT electronics versions are rated IP65. Plug-connected versions (standard pulse, F400, L443, and L442) use a DIN 43650 plug with a PG 11 cable gland. MA, WM, and K versions use a 1.5 m (4.9 ft) cable, or a connector, and E and G versions use a 10-pin cable or a pair of M12 connectors.
Product Specifications
Measuring Range
0.05...0.5 GPM to 0.8...15 GPM
Fittings
1/4"...3/4" NPT Thread
Body Materials
Brass, PTFE
Max. Pressure
70 PSIG / 230 PSIG
Max. Temperature
176 °F (80 °C)
Accuracy
± 2.5% or 5% FS (Model Dependent)
Product Features
Frequency Output Standard
Optional Digital Display, Analog Transmitters, Totalizer & Batch Controllers
No Straight Run Requirements
Compact, Economical Design