MWD Industrial Resistance Thermometer (Pt100 RTD)
The KOBOLD MWD is an industrial resistance thermometer (RTD) assembly that measures temperature from -324 to 1112 °F (-198 to 600 °C) with a Pt100 sensor per IEC 60751. Each assembly combines a rugged stainless steel installation fitting with a threaded, flanged, or weld-on process connection, a connection head, and a measuring element.
The sensor is available as a single or double Pt100 (1 x Pt100 or 2 x Pt100) with 2-wire, 3-wire, or 4-wire connection. The 4-wire version is built with one Pt100 only. The output is a resistance value, or a 4-20 mA signal when a head transmitter is fitted.
Temperature Range and Pt100 Accuracy Classes
The MWD is built in four measuring ranges set by the sensor type: -94 to 482 °F (-70 to 250 °C), -94 to 752 °F (-70 to 400 °C), -94 to 1112 °F (-70 to 600 °C), and a cryogenic range of -324 to 212 °F (-198 to 100 °C).
Pt100 accuracy classes are F0.3 (B), F0.15 (A), F0.1 (1/3 DIN), and F0.03 (1/10 DIN). Depending on the model, class F0.3 (B) and F0.15 (A) sensors are offered as single or double elements up to 1112 °F (600 °C). Class F0.1 and F0.03 sensors are single elements up to 752 °F (400 °C). The cryogenic sensor is a single Pt100.
MWD Models: Fixed and Removable Measuring Inserts
MWD models differ in how the measuring insert is installed. MWD-A, MWD-B, and MWD-L have a fixed insert in a protection tube. MWD-C, MWD-D, and MWD-E have an exchangeable insert in a protection tube. MWD-F, MWD-G, and MWD-W have an exchangeable insert without a protection tube and are mounted in a TWL-0 thermowell.
With a removable measuring insert, the element can be taken out without interrupting the process, because the thermowell remains in the installation and seals the process. Protection tube models are rated to 435 psi (30 bar) at 68 °F (20 °C), and models without a protection tube are rated for atmospheric pressure.
- MWD-A: compression fitting
- MWD-L: fixed thread
- MWD-B: thread or flange, with 5.12 in (130 mm) neck pipe
- MWD-C: thread
- MWD-E: compression fitting
- MWD-D: thread or flange, with 5.12 in (130 mm) neck pipe
- MWD-F: thread
- MWD-G: thread, with 5.12 in (130 mm) neck pipe
- MWD-W: thread, with 5.91 in (150 mm) nipple-union-nipple neck pipe
- MWD-M: measuring insert, for atmospheric pressure
- MWD-S and MWD-N: cable versions; cable limits are 176 °F (80 °C) for PVC, 392 °F (200 °C) for silicone, 428 °F (220 °C) for PTFE, and 662 °F (350 °C) for fiberglass with steel braid
- MWD-I and MWD-P: with PVC handle, for atmospheric pressure
- MWD-T: with aluminum or polycarbonate box rated to 176 °F (80 °C); protection tube without holes for outdoor installation or with holes for indoor installation
Process Connections, Materials, and Connection Heads
Process connections include G ¼ to G 1 and ¼" to 1" NPT male threads, DIN flanges DN 15 to DN 50 (PN 10, 16, and 40), ANSI flanges ½" to 2" (class 150 and class 300), and G ½ or ½" NPT compression fittings. The protection tube and measuring insert are stainless steel 1.4404 (316L).
Protection tubes and measuring inserts follow DIN 43772 (DIN 43763 on models MWD-S, N, I, P, and T), and the insert is filled with magnesium oxide (MgO). Tube diameters range from 0.12 to 0.47 in (3 to 12 mm) depending on the model, and the fitting length (EL) is specified with the order.
Connection heads are available in painted aluminum, stainless steel 1.4401, and polypropylene (PP), in screw-cap, DIN B, BUZ hinged-cover, and BUZ-H high hinged-cover styles. The standard electrical connection is M20 x 1.5. Ambient temperature is rated at -40 to 302 °F (-40 to 150 °C) with the ceramic terminal block and -40 to 185 °F (-40 to 85 °C) with a transmitter.
Head Transmitter and Output Options
An optional head transmitter, encapsulated in epoxy resin and located in the connection head, delivers a temperature-linear 4-20 mA output signal. Transmitters are available with HART protocol or Profibus/Fieldbus communication. Resistance thermometers with a head transmitter are used when the measuring signal has to be carried over a long distance.
- 5333D transmitter: 4-20 mA, 2-wire
- 5337D transmitter: 4-20 mA with HART protocol, 2-wire
- 5350A transmitter: Profibus PA or Foundation Fieldbus
- Prepared for later mounting of a transmitter, with 5.91 in (150 mm) flying leads
Transmitter versions use the 3-wire sensor connection, and the measuring range is specified with the order. An aluminum head with a backlit LCD display and an included HART transmitter is available on MWD-A, MWD-B, MWD-L, and MWD-W.
Applications
MWD resistance thermometers with thread and flange connections are used for temperature measurement in liquids, solids, and gaseous media. Application areas include HVAC, machinery, chemical and petrochemical industries, water, heating and cooling processes, and general industrial use. These installation methods are designed to seal against gauge pressure and vacuum.
Common Questions about MWD - Industrial Resistance Thermometers
A resistance thermometer uses the continuous change in electrical resistance of a metal as temperature rises and falls. The MWD sensor element is platinum, which is very stable and has very good repeatability. Platinum has a positive temperature coefficient, so its resistance increases with temperature. A Pt100 element has a nominal value of 100 Ω at 32 °F (0 °C).
Accuracy depends on the tolerance class selected. A class F0.3 (B) sensor has a tolerance of ±(0.3 + 0.005 × t) °C, and a class F0.15 (A) sensor ±(0.15 + 0.002 × t) °C, where t is the measured temperature in °C without sign. Classes F0.1 (1/3 DIN) and F0.03 (1/10 DIN) are also available.
Yes, on the versions built with an exchangeable insert. On MWD-C, MWD-D, and MWD-E, the protection tube stays in place and keeps the process closed while the insert is changed. MWD-F, MWD-G, and MWD-W also have exchangeable inserts and are installed in a TWL-0 thermowell.
MWD-A, B, C, D, E, and L, which have a protection tube, are rated to a maximum of 435 psi (30 bar) at 68 °F (20 °C). MWD-F, G, and W have no protection tube and are rated for atmospheric pressure, so they are used only with a TWL-0 thermowell. MWD-M, I, P, and T are atmospheric pressure versions.
The difference is how lead resistance affects the reading. A 2-wire circuit carries an error from the lead resistance. In a 3-wire circuit, lead resistance is negligible with connecting wires up to 82 ft (25 m). In a 4-wire circuit, the lead resistance of the connecting wires is negligible. Head transmitter options are ordered with 3-wire sensors.
The 5333D (4-20 mA) and 5337D (4-20 mA with HART) transmitters operate on an 8 to 35 V supply, and the 5350A (Profibus PA or Foundation Fieldbus) on 9 to 32 V. Absolute accuracy is ≤ ±0.54 °F (±0.3 °C) for the 5333D and ≤ ±0.18 °F (±0.1 °C) for the 5337D and 5350A.
An MWD order code is made up of the model, protection tube diameter, process connection, sensor type and class, RTD wiring, terminal head, head transmitter, and options. The fitting length (EL) is given in clear text. Transmitter versions also need the measuring range, and cable versions need the cable length (CL).
Wrong values combined with long response times point to the mounting geometry or to deposits on the sensor or thermowell. The temperature-sensitive area of the sensor must be inside the medium, and any deposits should be removed. Sensor drift caused by over-temperature is corrected by replacing the probe or measuring insert.
The MWD does not require maintenance or servicing, and repairs are carried out only by KOBOLD. In storage, the instrument should be protected against humidity and dust. A 3-point calibration report (DOK-FR05, additional points possible) and an inspection certificate 3.1 (DOK-FR03) can be ordered as accessories.
Connection head protection is IP54 to IP68, depending on the cable gland. The screw-cap, hinged-cover, and mini heads (options G, I, F, K, Z, H, and M) are IP65, and the DIN B screwed-cover head (option B) is IP54. The LCD display head (option E) is IP65.